Product Description
- brief introduction
- technical parameter
- Product size
Application
The DZ47LE residual current operated circuit breaker is applicable to the circuit with an alternating current of 50Hz, rated-voltage single pole and two lines/two poles 230V, three poles/three poles and four lines/four poles 400V, and a rated current 63~125A; when the human body gets an electric shock or the networkleakcurrent exceeds the specified value, the residual current operated circuit breaker can rapidly cut off the power supply in trouble within a very short time for the safety of the human body and the powered equipment. With the function of overload and short circuit protection, the residual current operated circuit breaker can be used to protect the circuit or motor from being damaged by overload and short circuit, and can also be used for not–frequent operational transformation in the circuit under normal condition.The product meets the standards of GB14048.2 and IEC60947-2.
Normal operating conditions
Ambient air temperature: -5°C~+40°C, the mean value is no greater than +35°C within 24 hours .
Altitude: not higher than 2000m for the installation site.
Installation category: III grade.
Pollution degree: 3.
Installation: TH35-7.5 DIN rail
Installation conditions: external magnetic field in any direction installation site should not exceed five times the Earth's magnetic field; residual current operated circuit breakers should be installed vertically, the handle for the power-up position; installation should be no significant impact and vibration.
Model
Main Technical Data
Main specifications
Poles: 1P + N, 2P, 3P, 3P + N, 4P;
Short circuit tripping characteristics: (8 ~ 12) In.
Technical parameters
Rated voltage Ue (V): 1P+N, 2P: 230;
? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? 3P, 3P+N, 4P: 400;
Rated current In (A): 63,80,100,125.
Frame rated current Inm (A): 125;
Rated residual operating current I△n (A): 0.03,0.1,0.3;
Rated residual non-operating current I△no (A): 0.5I△n;
Rated short-circuit breaking capacity Icu (A): 6000;
Rated residual making and breaking capacity I△ m (A): 2000;
Residual current breaking time ( Table 1).
For the over current protection characteristics ?( Table 2).
Mechanical/Electrical Life
a. Electrical life: no less than 1,500 times
b. Mechanical ?life: no less than 8,500 times
Insulation shock-resistance voltage performance: Uimp(V):4000; ?
The residual current operated circuit breaker has the capability of withstanding?
the impact of the surge current with a peak current of 200A without causing?misoperation;
Characteristic curve( Fig.1)
External And Installation Size